Squibb Taylor
Call us: 1.800.345.8105

RJ622E-DCH

Item Number124598
  • Inlet: 3/4" FNPT

  • Outlet: 3/4" FNPT

  • Outlet Pressure Range: 1 - 2.2 PSIG

  • Outlet Pressure Setting: 2 PSIG

  • Capacity in BTU/H LPG: 2,275,000 *

Case Quantity: 10 Pcs.

* Capacity in BTU per hour LPG:

     Based on 25 psig inlet pressure & 20% droop.

Maximum Allowable Inlet Pressure: 40 PSIG

Maximum Emergency Inlet Pressure: 50 PSIG

Orifice Size: 7/32"

Vent size: 3/4" NPT

Pressure Registration: Internal

Temperature Capabilities: -20°F to 160°F (1)

Type RJ622E - Second-stage regulators are designed for high pressure (pounds per square inch) vapor service. These regulators have high capacity internal relief valves. These regulators are intended for Jurisdictional Systems where the pressure coming from the first-stage is higher than 10 psig. The Type RJ622E standard outlet pressure setting is 2 psig. It is an intermediate stage regulator that reduces 10 psig first stage pressure to 2 psig. They are used on 2 psig pressure systems. Based on the R600 Series product line, the RJ600 Series offers the same features, benefits and proven performance; The maximum inlet was increased in order to meet the requirements of a Jurisdictional System. Screened drip-lip vent has standard orientation over the inlet with other orientations available. RJ622E Series regulators are painted palm green with a white cap for easy identification. Types RJ622E are not suitable for first stage service.

1. Product has passed Fisher® testing for leakage down to -40°F / -40°C.